Radiant tube heater sizing calculator

Size gas radiant tube heaters for a shop, pole barn or warehouse: the input BTU, how many heaters, and how high to hang them.

Your building

Building
Heat loss
Insulation

Radiant tube heaters

2 × 50,000 Btu/h

This building loses about 63,400 Btu/h at 20°F. With Roberts-Gordon's 0.80 radiant credit, the heaters need 50,700 Btu/h of input.

60 ft
Along the long walls, where the building loses most heat
50,700Btu/h input with the 0.80 radiant credit
2heaters at the full heat loss (Modine)
Total input
100,000 Btu/h
Burner height
12 ft
Between burners
10–15 ft
Burner to wall
3–15 ft
Between rows
40–50 ft
Tube lengths
20, 30 ft

Home garage: many tube heaters, including Roberts-Gordon CTH and Detroit Radiant DR, are not for residential use. Detroit Radiant's LD and LS (25,000–50,000 Btu/h) include models certified for residential garages.

Compare in the shop heater BTU calculator →

Updated

Tube heater sizes for common buildings

Average insulation, a 20°F winter low, kept at 60°F, two or three overhead doors. The heater size is the largest one rated for a burner height just under the ceiling that does not exceed the load.

BuildingHeat lossInput at 0.80HeatersAt full heat loss
30 × 40 × 14 ft33,600 Btu/h26,900 Btu/h1 × 50,0001 × 50,000
40 × 60 × 16 ft63,400 Btu/h50,700 Btu/h2 × 50,0002 × 50,000
60 × 100 × 20 ft164,000 Btu/h131,200 Btu/h2 × 125,0002 × 125,000
100 × 200 × 24 ft560,500 Btu/h461,900 Btu/h3 × 200,0003 × 200,000

How the radiant credit works

Heat loss first. The calculator works out the building's steady heat loss through walls, roof, overhead doors, the slab edge and air leaks at your winter low, using the same model as the shop heater BTU calculator but without the warm-up allowance a forced-air heater gets. If an engineer or supplier has already given you a design heat loss, choose "I have a number" and enter it.

Then the radiant adjustment. Roberts-Gordon's CORAYVAC design manual multiplies the heat loss by 0.80, from studies that put the factor between 0.80 and 0.85. ASHRAE's handbook gives the same 80 to 85% range. Radiant heat warms the slab and objects, so the air can run cooler, less heat stratifies under the roof and less leaks out with the air.

Then the height. Hung higher, less of the heat reaches the floor, so Roberts-Gordon adds 1% for every foot above 20 ft, up to 60 ft. Its worked example: a 350,000 Btu/h heat loss with burners at 30 ft needs 308,000 Btu/h of input (350,000 × 0.80 × 1.10). At 50 ft the credit is almost gone: 500,000 × 0.80 × 1.30 = 520,000.

Not every maker takes the credit. Modine's design guide replaces the heat loss with at least the same input, which is why the result also shows the heater count at the full heat loss. The gap between the two is your safety margin for very cold nights.

How many heaters, and where they go

Divide the input you need by one heater's input and round up. Modine's example: a 200 × 160 ft building losing 1,600,000 Btu/h needs 13 heaters of 125,000 Btu/h (1,600,000 ÷ 125,000 = 12.8). Fewer, bigger heaters mean fewer gas and vent connections; more, smaller ones spread the heat more evenly.

Heat leaves a building mostly through its outside walls and doors, so the tubes go along the perimeter. When the long walls are more than 100 ft apart, Modine adds rows down the middle to cover the roof loss, with at least 80% of the capacity still on the perimeter. Put extra output by an overhead door that opens often or a north wall.

Mounting height and spacing by heater size

Modine's suggested placement for low-intensity tube heaters in whole-building heating, in feet. The calculator uses these ranges to pick a size for your ceiling and to warn when a chosen size hangs too low or too high. Clearances to combustibles differ by model and by which way the reflector faces, so take them from the heater's own manual.

Input (Btu/h)Burner heightBetween burnersBurner to wallBetween rowsTube lengths
50,00010–1210–153–1540–5020, 30
60,00010–1210–153–1540–5020, 30, 40
75,00012–1410–253–1550–6020, 30, 40
100,00012–1415–353–2560–7030, 40, 50
125,00015–2215–383–2860–7040, 50, 60
150,00015–2515–453–3060–8050, 60
175,00018–2820–504–3560–8050, 60, 70
200,00020–3025–604–4060–8050, 60, 70

Tube heaters in a home garage

Most tube heaters are built for commercial buildings, and many are labelled not for residential use, including Roberts-Gordon's CTH and Detroit Radiant's DR series. For a home garage, look for a model the maker lists as certified for residential use, such as some of Detroit Radiant's low-mount LD and LS heaters (25,000 to 50,000 Btu/h, 10 to 30 ft tubes). With a ceiling under about 11 ft, Modine's table has no size, and an electric infrared heater over the work area is often the simpler choice.

Questions people ask

How do you size a radiant tube heater?

Start from the building's design heat loss, multiply by a radiant adjustment (Roberts-Gordon uses 0.80), add 1% for each foot of mounting height above 20 ft, then divide by the heater's input and round up. Our default 40 × 60 × 16 ft shop loses about 63,400 Btu/h at 20°F, which becomes 50,700 Btu/h of input: 2 × 50,000 Btu/h heaters.

How many BTU tube heater do I need for a 40 × 60 shop?

With a 16 ft ceiling, average insulation and a 20°F winter low, about 50,700 Btu/h of input with the radiant credit, or 63,400 Btu/h if you size at the full heat loss as Modine's guide does. That is two 50,000 Btu/h heaters hung at 12 ft, one along each long wall.

Why do radiant heaters need fewer BTUs than forced air?

They heat the floor, machines and people instead of the air, so the air can stay cooler, less heat collects under the roof and less leaks out. Roberts-Gordon's design manual puts the reduction at 15 to 20% (factors 0.80 to 0.85), ASHRAE's handbook says manufacturers should recommend 80 to 85% of the heat loss, and Auburn University's extension engineers report about 15% less capacity in practice.

How high should a radiant tube heater be mounted?

Bigger burners hang higher. Modine's design guide rates 50,000 and 60,000 Btu/h heaters for 10 to 12 ft, 100,000 for 12 to 14 ft, 150,000 for 15 to 25 ft and 200,000 for 20 to 30 ft. Too low and it is too hot underneath; too high and too little heat reaches the floor. Leave the top clearance the heater's manual asks for, often 12 in on top.

Where should tube heaters go in a building?

Along the outside walls, where the heat is lost. Modine puts at least 80% of the capacity on the perimeter and adds centre rows, with at most 20%, only when the long walls are more than 100 ft apart. See spacing for each size.

Can I put a tube heater in my home garage?

Only a model certified for residential use. Many tube heaters, such as Roberts-Gordon's CTH and Detroit Radiant's DR series, are labelled not for residential use. Detroit Radiant's low-mount LD and LS series (25,000 to 50,000 Btu/h) include models CSA design-certified for residential garages.

Is a tube heater better than a unit heater for a shop?

For a tall, drafty shop with big doors, often yes: the slab stores heat and recovers fast after the door closes. For a small, low garage heated for an hour at a time, a vented unit heater warms the air faster. Use the shop heater BTU calculator.

Sources

Sources last checked November 27, 2026.

  1. Roberts-Gordon, CORAYVAC SF Design Manual (127502NA) (accessed November 27, 2026) · radiant adjustment 0.80–0.85 (0.80 used); +1% per ft above 20 ft up to 60 ft; 350,000 × 0.80 × 1.10 = 308,000
  2. Modine, Infrared Heater Design Guide 9-200.7 (accessed November 27, 2026) · heaters = heat loss ÷ input; 80/20 perimeter rule; Tables 4.1 and 12.1 mounting height and placement
  3. ASHRAE Handbook, HVAC Systems and Equipment, Ch. 16 Infrared Radiant Heating (accessed November 27, 2026) · rated output 80 to 85% of the heat loss (Buckley and Seel 1988)
  4. Auburn University, Radiant Tube Heaters for Poultry Houses (undated) · manufacturers recommend around 15% less capacity than forced air
  5. Roberts-Gordon, CTH tube heater specifications (accessed November 27, 2026) · not for residential use
  6. Detroit Radiant Products, product catalog (accessed November 27, 2026) · DR series not for residential use; LD/LS 25,000–50,000 Btu/h, select models CSA certified for residential garages